Rating record
Derating factors: the drum rating is not the rating in the tray
Accepted inputs
- Load
- 43.000 A
- Loaded circuits bunched together
- 4
- Ambient factor
- 0.900000
- Installation factor
- 0.800000
- Entry 1 Label
- Size 10
- Entry 1 Base rating
- 40.000 A
- Entry 2 Label
- Size 16
- Entry 2 Base rating
- 60.000 A
- Entry 3 Label
- Size 25
- Entry 3 Base rating
- 90.000 A
- Count 1
- 1.000000
- Count 2
- 1.000000
- Count 3
- 1.000000
- Count 4
- 1.000000
- Count 5
- 0.800000
- Count 6
- 0.800000
- Count 7
- 0.800000
- Count 8
- 0.800000
- Count 9
- 0.600000
- Count 10
- 0.600000
- Count 11
- 0.600000
- Count 12
- 0.600000
- Count 13
- 0.600000
- Count 14
- 0.600000
- Count 15
- 0.600000
- Count 16
- 0.600000
- Count 17
- 0.600000
- Count 18
- 0.600000
- Count 19
- 0.600000
- Count 20
- 0.600000
All results
- Tracked answer
- Size 16
- Load
- 43.000 A
- Combined factor
- 0.72
- Selected entry
- Size 16
- Base rating
- 60.000 A
- Resulting rating
- 43.200 A
- margin
- 0.200 A
- Entry below
- Size 10 28.800 A
- Entry above
- Size 25 64.800 A
- Size 10
- 40.000 A, 28.800 A, no
- Size 16
- 60.000 A, 43.200 A, yes
- Size 25
- 90.000 A, 64.800 A, yes
- Ambient factor
- 0.900000
- Installation factor
- 0.800000
- Grouping at 4 circuits
- 1.000000
- Combined factor
- 0.72
Sweep of Loaded circuits bunched together
- The assumption
- Loaded circuits bunched together
- Values sampled
- 1 to 20 circuits, 20 values, step 1
- The answer
- Size 16
- Holds across
- 1 to 4 circuits
- Nearest change
- 5 circuits, where it becomes Size 25
- Reading the boundary
- The sweep samples only the values you entered. Between samples the answer is not checked, so read the boundary as observed, not proven.
Record fields
- Calculation version
- 1.0.0
- Boundary
- This page sizes nothing and is not a design. It multiplies the factors you typed and does nothing else. It holds no standard's tables, certifies nothing, and cannot see which factors apply to your installation.
- Calculation trace
- Multiply ambient, installation, grouping and every additional factor. Multiply each base rating by the combined factor. Walk the declared list in order and stop at the first result that covers the load.
- Source anchor
- IEC public scope page for IEC 60364-5-52